2.2-kW IPMSM, dual-voltage-forming AFE, CVC
===========================================

This example simulates a 2.2-kW interior permanent-magnet synchronous machine (IPMSM)
drive whose active front end (AFE) uses dual-voltage-forming control [#Mou2025]_ and is
connected to a weak grid. The grid-side converter regulates both the DC-bus voltage and
its output voltage magnitude without a cascaded DC-bus voltage controller: the external
power fed to the DC bus by the drive is estimated by a disturbance observer and fed
forward. The machine-side converter uses sensorless current-vector control (CVC). The
two control systems are independent: they have different sampling periods, and their
carriers are not synchronized. The system model is otherwise the same as in
:doc:`/drive_examples/grid_connection/plot_2kw_ipmsm_afe_cvc`, except for the weak grid.

.. GENERATED FROM PYTHON SOURCE LINES 18-30

.. code-block:: Python

    from math import pi

    import matplotlib.pyplot as plt

    import motulator.drive.control.sm as sm_control
    from motulator.common.model import CompositeModel, DCBus, Simulation, ThreePhaseSource
    from motulator.drive import model as drive_model
    from motulator.drive import utils as drive_utils
    from motulator.grid import control as grid_control
    from motulator.grid import model as grid_model
    from motulator.grid import utils as grid_utils








.. GENERATED FROM PYTHON SOURCE LINES 31-32

Compute base values based on the nominal values of the machine and the grid converter.

.. GENERATED FROM PYTHON SOURCE LINES 32-38

.. code-block:: Python


    nom_m = drive_utils.NominalValues(U=370, I=4.3, f=75, P=2.2e3, tau=14)
    base_m = drive_utils.BaseValues.from_nominal(nom_m, n_p=3)
    nom_g = grid_utils.NominalValues(U=400, I=5, f=50, P=2.2e3)
    base_g = grid_utils.BaseValues.from_nominal(nom_g)








.. GENERATED FROM PYTHON SOURCE LINES 39-41

Configure the system model. The two converters are fed from the same DC bus. The grid
is weak: its inductance is 0.74 p.u.

.. GENERATED FROM PYTHON SOURCE LINES 41-61

.. code-block:: Python


    afe = grid_model.VoltageSourceConverter(modulator=grid_model.CarrierComparison())
    inv = drive_model.VoltageSourceConverter(modulator=drive_model.CarrierComparison())
    dc_bus = DCBus(C_dc=470e-6, u_dc=650)

    ac_filter = grid_model.LFilter(
        L_f=0.15 * base_g.L, R_f=0.05 * base_g.Z, L_g=0.74 * base_g.L
    )
    ac_source = ThreePhaseSource(w_g=base_g.w, e_g=base_g.u)
    grid_sys = grid_model.GridConverterSystem(afe, ac_filter, ac_source, dc_bus=dc_bus)

    par = drive_model.SynchronousMachinePars(
        n_p=3, R_s=3.6, L_d=0.036, L_q=0.051, psi_f=0.545
    )
    machine = drive_model.SynchronousMachine(par)
    mechanics = drive_model.MechanicalSystem(J=0.015)
    drive_sys = drive_model.Drive(machine, mechanics, inv, dc_bus=dc_bus)

    mdl = CompositeModel({"grid": grid_sys, "drive": drive_sys})








.. GENERATED FROM PYTHON SOURCE LINES 62-66

Configure the control systems. The grid-side control runs at 10 kHz (5-kHz switching
frequency) and the machine-side control at 8 kHz (4-kHz switching frequency). The
gains of the dual-voltage-forming controller are given in per-unit values of the grid
converter [#Mou2025]_.

.. GENERATED FROM PYTHON SOURCE LINES 66-94

.. code-block:: Python


    cfg_g = grid_control.DualVoltageFormingControllerCfg(
        i_max=1.5 * base_g.i,
        L=0.3 * base_g.L,
        C_dc=470e-6,
        R=0.05 * base_g.Z,
        k_d=base_g.u / base_g.p,
        alpha_dc=0.15 * base_g.w,
        alpha_o=2 * base_g.w,
        alpha_o_dc=1.2 * base_g.w,
        k_v=6,
        alpha_c=6 * base_g.w,
        u_nom=base_g.u,
        w_nom=base_g.w,
        T_s=100e-6,
    )
    ctrl_g = grid_control.GridConverterControlSystem(
        grid_control.DualVoltageFormingController(cfg_g)
    )

    est_par = par  # Assume accurate model parameter estimates
    cfg_m = sm_control.CurrentVectorControllerCfg(
        i_s_max=1.5 * base_m.i, alpha_o=2 * pi * 100, T_s=125e-6
    )
    vector_ctrl = sm_control.CurrentVectorController(est_par, cfg_m)
    speed_ctrl = sm_control.SpeedController(J=0.015, alpha_s=2 * pi * 4)
    ctrl_m = sm_control.VectorControlSystem(vector_ctrl, speed_ctrl)








.. GENERATED FROM PYTHON SOURCE LINES 95-97

Set the references and the external load torque. The speed is reversed under load,
after which the drive regenerates power to the grid.

.. GENERATED FROM PYTHON SOURCE LINES 97-103

.. code-block:: Python


    ctrl_g.set_dc_bus_voltage_ref(650)
    ctrl_g.set_ac_voltage_ref(base_g.u)
    ctrl_m.set_speed_ref(lambda t: (t > 0.1) * base_m.w_M - (t > 0.7) * 2 * base_m.w_M)
    mechanics.set_external_load_torque(lambda t: (t > 0.4) * nom_m.tau)








.. GENERATED FROM PYTHON SOURCE LINES 104-107

Create the simulation object and simulate. The clocks of the two control systems are
not synchronized: the machine-side control starts 40 µs after the grid-side control.
The results of each model and its control system are available by the model names.

.. GENERATED FROM PYTHON SOURCE LINES 107-113

.. code-block:: Python


    sim = Simulation(mdl, {"grid": ctrl_g, "drive": ctrl_m}, t_start={"drive": 40e-6})
    res = sim.simulate(t_stop=1)
    res_drive = drive_model.SimulationResults(res.mdl.drive, res.ctrl.drive)
    res_grid = grid_model.SimulationResults(res.mdl.grid, res.ctrl.grid)








.. GENERATED FROM PYTHON SOURCE LINES 114-117

Plot the drive and grid-side results in per-unit values. The active power reference
shown is the equivalent reference formed by the dual-voltage-forming controller from
the estimated external power and the DC-bus energy error.

.. GENERATED FROM PYTHON SOURCE LINES 117-122

.. code-block:: Python


    # sphinx_gallery_thumbnail_number = 3
    drive_utils.plot(res_drive, base_m)
    grid_utils.plot_control_signals(res_grid, base_g)




.. rst-class:: sphx-glr-horizontal


    *

      .. image-sg:: /drive_examples/grid_connection/images/sphx_glr_plot_2kw_ipmsm_afe_dvf_cvc_001.png
         :alt: plot 2kw ipmsm afe dvf cvc
         :srcset: /drive_examples/grid_connection/images/sphx_glr_plot_2kw_ipmsm_afe_dvf_cvc_001.png
         :class: sphx-glr-multi-img

    *

      .. image-sg:: /drive_examples/grid_connection/images/sphx_glr_plot_2kw_ipmsm_afe_dvf_cvc_002.png
         :alt: plot 2kw ipmsm afe dvf cvc
         :srcset: /drive_examples/grid_connection/images/sphx_glr_plot_2kw_ipmsm_afe_dvf_cvc_002.png
         :class: sphx-glr-multi-img





.. GENERATED FROM PYTHON SOURCE LINES 123-128

Plot the DC-bus voltage and the power balance: the estimated external power fed to the
DC bus (the estimated disturbance power plus the grid power and the resistive losses
of the filter) follows the mechanical power plus the losses (mainly the stator
resistive losses), and the power drawn from the grid follows it with the delay of the
current dynamics in the weak grid.

.. GENERATED FROM PYTHON SOURCE LINES 128-154

.. code-block:: Python


    ctrl_ts = res.ctrl.grid
    p_loss = 1.5 * cfg_g.R * abs(ctrl_ts.fbk.i_c) ** 2
    p_ext = ctrl_ts.fbk.p_dis + ctrl_ts.fbk.p_g + p_loss
    p_M = res.mdl.drive.machine.tau_M * res.mdl.drive.machine.w_M
    fig, (ax1, ax2) = plt.subplots(2, 1, sharex=True)
    ax1.plot(res.mdl.t, res.mdl.drive.dc_bus.u_dc, label=r"$u_\mathrm{dc}$")
    ax1.plot(
        ctrl_ts.t,
        ctrl_ts.ref.u_dc,
        "--",
        ds="steps-post",
        label=r"$u_\mathrm{dc}^\mathrm{ref}$",
    )
    ax1.set_ylabel("Voltage (V)")
    ax1.legend()
    ax2.plot(ctrl_ts.t, -p_ext / 1e3, ds="steps-post", label=r"$-\hat{p}_\mathrm{ext}$")
    ax2.plot(
        ctrl_ts.t, -ctrl_ts.fbk.p_g / 1e3, ds="steps-post", label=r"$-\hat{p}_\mathrm{g}$"
    )
    ax2.plot(res.mdl.t, p_M / 1e3, label=r"$\tau_\mathrm{M}\omega_\mathrm{M}$")
    ax2.set_ylabel("Power (kW)")
    ax2.set_xlabel("Time (s)")
    ax2.legend()
    plt.show()




.. image-sg:: /drive_examples/grid_connection/images/sphx_glr_plot_2kw_ipmsm_afe_dvf_cvc_003.png
   :alt: plot 2kw ipmsm afe dvf cvc
   :srcset: /drive_examples/grid_connection/images/sphx_glr_plot_2kw_ipmsm_afe_dvf_cvc_003.png
   :class: sphx-glr-single-img





.. GENERATED FROM PYTHON SOURCE LINES 155-157

Plot the grid-side waveforms around the load torque step. The converter current
increases within a few milliseconds, as the estimated external power is fed forward.

.. GENERATED FROM PYTHON SOURCE LINES 157-162

.. code-block:: Python


    grid_utils.plot_grid_waveforms(
        res_grid, base_g, t_lims=(0.39, 0.45), plot_pcc_voltage=False
    )




.. image-sg:: /drive_examples/grid_connection/images/sphx_glr_plot_2kw_ipmsm_afe_dvf_cvc_004.png
   :alt: plot 2kw ipmsm afe dvf cvc
   :srcset: /drive_examples/grid_connection/images/sphx_glr_plot_2kw_ipmsm_afe_dvf_cvc_004.png
   :class: sphx-glr-single-img





.. GENERATED FROM PYTHON SOURCE LINES 163-168

.. rubric:: References

.. [#Mou2025] Mourouvin, Nurminen, Hinkkanen, Routimo, "Direct DC-bus control for
   grid-forming converters: Toward the concept of dual-voltage-forming converters,"
   IEEE Trans. Power Electron., 2025, https://doi.org/10.1109/TPEL.2025.3537332


.. rst-class:: sphx-glr-timing

   **Total running time of the script:** (0 minutes 51.666 seconds)


.. _sphx_glr_download_drive_examples_grid_connection_plot_2kw_ipmsm_afe_dvf_cvc.py:

.. only:: html

  .. container:: sphx-glr-footer sphx-glr-footer-example

    .. container:: sphx-glr-download sphx-glr-download-jupyter

      :download:`Download Jupyter notebook: plot_2kw_ipmsm_afe_dvf_cvc.ipynb <plot_2kw_ipmsm_afe_dvf_cvc.ipynb>`

    .. container:: sphx-glr-download sphx-glr-download-python

      :download:`Download Python source code: plot_2kw_ipmsm_afe_dvf_cvc.py <plot_2kw_ipmsm_afe_dvf_cvc.py>`

    .. container:: sphx-glr-download sphx-glr-download-zip

      :download:`Download zipped: plot_2kw_ipmsm_afe_dvf_cvc.zip <plot_2kw_ipmsm_afe_dvf_cvc.zip>`


.. only:: html

 .. rst-class:: sphx-glr-signature

    `Gallery generated by Sphinx-Gallery <https://sphinx-gallery.github.io>`_