10-kVA converter, LCL filter#
This example simulates a grid-following-controlled converter connected to a strong grid through an LCL filter. The control system includes a phase-locked loop (PLL) to synchronize with the grid, a current reference generator, and a PI-type current controller.
from motulator.common.model import VoltageSourceConverter, Simulation
from motulator.common.utils import BaseValues, NominalValues
from motulator.grid import model
import motulator.grid.control.grid_following as control
from motulator.grid.utils import FilterPars, GridPars, plot
Compute base values based on the nominal values.
nom = NominalValues(U=400, I=14.5, f=50, P=10e3)
base = BaseValues.from_nominal(nom)
Configure the system model.
# Grid and filter parameters
grid_par = GridPars(u_gN=base.u, w_gN=base.w)
filter_par = FilterPars(L_fc=.073*base.L, L_fg=.073*base.L, C_f=.043*base.C)
# DC-bus parameters
ac_filter = model.ACFilter(filter_par, grid_par)
# AC grid model with constant voltage magnitude and frequency
grid_model = model.ThreePhaseVoltageSource(w_g=base.w, abs_e_g=base.u)
# Inverter model with constant DC voltage
converter = VoltageSourceConverter(u_dc=650)
# Create system model
mdl = model.GridConverterSystem(converter, ac_filter, grid_model)
Configure the control system.
# Control parameters
cfg = control.GFLControlCfg(grid_par, filter_par, max_i=1.5*base.i)
# Create the control system
ctrl = control.GFLControl(cfg)
Set the time-dependent reference and disturbance signals.
# Set the active and reactive power references
ctrl.ref.p_g = lambda t: (t > .02)*5e3
ctrl.ref.q_g = lambda t: (t > .04)*4e3
Create the simulation object and simulate it.
sim = Simulation(mdl, ctrl)
sim.simulate(t_stop=.1)
Plot the results.
plot(sim, base)